A heat pump needs its own circuit, a breaker sized from its nameplate, and a disconnect in the fixed wiring. In a house with no gas, the electric backup heat decides whether the panel can carry it. Ask for the heat kit size first. The heat pump comes second.
This isn’t urgent. You’ll want to book ahead. Make the call before the HVAC contract is signed, not after the unit is sitting on its pad.
Gas, propane or oil changes the answer
Start with how the house is heated today. That one detail sorts most of it.
Adding an air-source unit to a furnace you keep? Natural Resources Canada says it generally needs no service upgrade. Going all-electric, air-source or ground-source? NRCan’s words are a 200 ampere service, normally. Leaving natural gas or fuel oil behind? The panel may need an upgrade.
What about propane or oil? Keep the old furnace as the backup and you have a hybrid. NRCan says a hybrid runs the heat pump or the furnace, never both at once. The panel sees one load at a time.
Pull the furnace out and it’s all-electric. The backup is then resistance heat in the ductwork or baseboards, and NRCan says those can run at the same time as the heat pump. That’s the case that breaks a calculation.
Same heat pump, different house, different answer. We stop at the meter; the utility owns everything up to it. In our judgment, an older village house in Elmvale or Phelpston and a newer estate lot near Midhurst shouldn’t get the same panel advice until someone has run the numbers. Both houses need the heat kit number before anyone talks panel. When you call an electrician in Springwater about a heat pump, ask for the load calculation by name.
The nameplate sets the circuit
Every outdoor unit carries a label. Two numbers on it matter: the minimum circuit ampacity and the maximum overcurrent protection.
The wire is sized from the first. The breaker can’t exceed the second. GE’s manual for its split heat pumps says the acceptable fuses or breakers are specified on the nameplate of each unit. For the larger of its two outdoor units, it recommends 45 amps.
Can it share a circuit with the dryer? No. The ACiQ manual says connect the unit to an individual branch circuit and connect no other appliance to it. The same manual calls for a switch or breaker in the fixed wiring that disconnects all poles.
A sales sheet that says “3 tons” tells us nothing about the wire. The label does.
The heat kit is the real load
Here’s why the kit matters. NRCan puts the minimum operating temperature of newer air-source units between -15°C and -25°C. Below that, a supplemental system has to carry the house.
In an all-electric house, that supplement is an electric heat kit. Look at what GE specifies for its own kits. The table shows the numbers.
| GE equipment | Breaker |
|---|---|
| 10 kW heat kit | One 60 amp |
| 20 kW heat kit | Two 60 amp |
| Outdoor unit | 35 or 45 amp |
The backup heat can need more breaker than the heat pump itself.
The question to ask the HVAC installer isn’t “how big is the heat pump?” It’s “what size heat kit are you putting in?” Until that’s picked, nobody can tell you whether your existing service passes.
The paperwork
ESA keeps a separate small-jobs form for HVAC equipment, and a heat pump is on its list, filed when the job is ready for final inspection.
Who files it? ESA says the person doing the work, you or a Licensed Electrical Contractor. Our page on ESA notification of work vs permit covers what that filing gives you. ESA issues the Certificate of Acceptance to whoever filed. Ask for a copy.
What we won’t do
- Size the service before the heat kit is picked. A 10 kW kit and a 20 kW kit are different panels.
- Put the heat pump on a shared circuit. GE’s manual says a dedicated circuit. ACiQ’s says an individual branch circuit.
- Wire from the brochure. We wire from the nameplate on the unit that’s actually going in.
- Call the existing service fine without the numbers. It might be. The calculation says so, not us.
Before you sign the HVAC contract
If the heat pump replaces the only furnace, think about the next outage too. Whether a given generator starts a given heat pump depends on the unit’s starting draw, which is on the nameplate. We size the backup from that, not from the brochure. A generator installation for a Barrie-area house belongs in the same plan, and we pick portable inlet or transfer switch after the nameplate is read.
What should you have in hand when you call? The fuel the house burns now, whether the furnace stays, and the heat kit size on the HVAC quote. Describe those three things on the phone, and we say whether it is a circuit, a panel upgrade in the Barrie area, or a service upgrade.
