If the charger stays with the house, hardwire it. In Ontario a plug-in on a NEMA 14-50 needs a 50 A breaker and tops out at 40 A of charging. A hardwired unit reaches 48 A on a 60 A circuit, or it can be turned down to fit a panel with little room left. The plug-in wins one case: you’re taking the charger with you when you move.
Speed isn’t the first question, though. The panel is. Which one fits depends on how much room your service has, and that’s a calculation, not a preference.
The two side by side
| Plug-in (NEMA 14-50) | Hardwired | |
|---|---|---|
| Most charging current | 40 A (ChargePoint, SWTCH) | 48 A (Tesla, SWTCH), up to 50 A (ChargePoint) |
| Breaker in Ontario | 50 A, set by ESA | Matched to the setting: Tesla lists 15 A to 60 A |
| Can be set lower to fit the panel | No: a cord-connected charger counts at nameplate unless it is fixed in place | Yes, with a label and a locked setting |
| Ground fault protection | Ask which device provides it | Built into some units, such as Tesla’s |
| Moves with you | Yes | Needs an electrician to take down |
The charger on SWTCH’s shop page shows the trade in one line. You pick a plug at 40 A or a wired unit at 48 A.
Ontario picks the breaker for a plug-in
ChargePoint’s install page lists two plug-in options for its Home Flex: 32 A on a 40 A breaker, or 40 A on a 50 A breaker. In Ontario, the 32 A option on a 40 A breaker is ruled out for a 14-50 receptacle. The 40 A setting on a 50 A breaker stays.
Ontario Electrical Safety Code Bulletin 86-1-7 came out in May 2025, from the Electrical Safety Authority. It says a 14-50R or 6-50R used for a cord-connected charger has to sit on a 50 A overcurrent device. That’s the rule, and it’s ESA’s, not ours.
Can’t I just set the app to 32 A? You can. The breaker stays 50 A. A cord-connected charger that is not fixed in place counts at its full nameplate, 40 A, in the load calculation. The bulletin allows a turned-down setting on fixed-in-place equipment only. A tight panel needs that turn-down, and a plug-in on a 14-50 cannot give it.
Why a hardwired charger fits a tight panel
The same bulletin answers the next question. Can a charger count at its turned-down setting instead of its nameplate? Yes, on three conditions.
- Fixed in place. The bulletin defines that as a mount you need a tool to remove.
- A permanent label. It goes on or beside the charger and lists the setting, the breaker and the wire size.
- A locked setting. A tool, a site password or the maker’s own lockout keeps the owner out of it.
A hardwired charger meets the first by design. That’s why it’s the flexible choice on an older service. Tesla’s Gen 3 manual pairs breakers from 15 A to 60 A with a matching output: 32 A on a 40 A breaker, 24 A on a 30 A breaker.
One more detail from the bulletin. A charger limited to 48 A on a 60 A circuit doesn’t need its own separate disconnect. Turn it up to 64 A on an 80 A circuit and it does.
If even a turned-down charger won’t fit, ESA names two ways forward: an energy management system, or a service upgrade. The second one is an electrical panel upgrade in Barrie, and it’s the bigger job.

Ground fault protection sits in one place
Some hardwired chargers carry their own. Tesla’s Gen 3 manual says it has integrated GFCI and tells the installer not to add a GFCI breaker. ChargePoint calls hardwiring the best option outdoors, and where local code wants a GFCI breaker.
Ask your installer one question. Which device protects this charger? You want one answer, not two devices arguing.
If you want the plug-in anyway
Moving in a few years? Then a plug-in is fair. Make it a proper one.
- The receptacle. A plug-in charger pulls 40 A for hours, so the receptacle matters. Ask for an industrial-grade receptacle, such as a Hubbell or Bryant, and ask for the brand on the invoice.
- The breaker. 50 A, because ESA says so. The charger is set to 40 A or less.
- No adapters. Tesla’s Mobile Connector manual forbids extension cords, multi-plugs, conversion plugs and power strips. On a 14-50 that Mobile Connector only draws 32 A anyway.
- Winter. In cold weather outdoors, keep the receptacle under cover. Tesla says don’t plug into an outlet covered in snow. If it’s already plugged in and buried, turn off the breaker before you unplug.
What we won’t do
- Fit a 14-50 on a 40 A breaker because the app is set low. ESA requires 50 A.
- Count a plug-in at its turned-down setting. The bulletin allows that on fixed equipment only.
- Turn a hardwired charger down without the label and the lock. Without both, it counts at full nameplate.
- Tell you an extension cord will do until the circuit’s in. Tesla’s manual forbids it.
The permit and the run are the same
A new 240 V circuit is notified to ESA either way. Our post on the EV charger permit in Ontario covers who files it and the paper you keep. The circuit from the panel to the garage is the same run too. Only the last foot differs: a receptacle or a wired box.
That’s why a quote that’s much cheaper for the plug-in deserves a question. What receptacle is it, and what breaker?
How to decide
- Get the load calculation first. Our guide to an EV charger on a 100 amp service shows what it counts.
- No room for a 50 A circuit? Hardwire, and set the charger to what fits.
- Room to spare? Then it’s about moving. Staying put means hardwired. Moving soon means a plug-in on a good receptacle and a 50 A breaker.
- Short commute? Check whether a Level 1 EV charger covers your week before you buy either.
Tell us what’s in the panel and what car is coming. Then ask for the load calculation before anyone picks a charger, ours included. That’s step one of EV charger installation around Barrie, not an extra.